AGIL modular UPS


1. SYSTEM Description

 

For critical application, continuity of service is essential. Migration, decentralisation, of IT equipment experiences daily change through new technologies needs a UPS concept that is a modular design based.

CE+T modular UPS concept is innovative and the foundation of high power protection availability of critical infrastructure for data-centre, process control, financial organisation.

CE+T AGIL is a rack modular design which offer 3 types of frames that addresses output power from 20 kVA up to 640 kVA.

 

The key features of CE+T AGIL UPS:

  • Unity power factor at AC input reducing AC input THD to 0

  • High efficiency 97% in both DC & AC operation mode

  • Scalability to add power as you growth

  • Extremely high power density

  • No need of high qualified maintenance

 

The Key features of CE+T modular UPS are:

  • Maximum efficiency at low load. 95% at 30% load

  • No single point of failure due to modular concept. No need of external static switch

  • Smooth transfer from AC to Battery without moving part (relay) or switches

  • No transfer time from AC to DC.

  • Unity power factor correction

  • 10xIn during 20 mS following condition. Optional triac board must present, AC In must present, and Agil not use as AC/AC converter.

  • High short circuit capability to guarantee total selectivity in AC distribution

  • AC to AC converter (single phase to three phases, three phase to single phases, 50Hz to 60Hz, 60Hz to 50Hz.

 

We focus our development on complete solution offered which includes

  • Frame to receive module and battery when possible.

  • Battery extension frame or shelve for expanded autonomy

  • Local and remote monitoring solution.

 

2. Technical Characteristics UPS 20 to 640 kVA

 

2.1 Mechanical for frames and modules

Model

Frame 20-60 kVA

Frame 40 to 160 kVA single

Frame 40 to 160 kVA expandable up to 4 bays in parallel

 

 

 

 

Standard Config.

20 kVA expandable to 60 kVA

40 kVA expandable to 160 kVA

External Battery

40 kVA expandable to 640 kVA (maximum 4 frames in parallel).

Nominal Power Max.

60 kVA

160 kVA

640 kVA

Dimension

600x800x2100 mm

600x800x2100 mm

600x800x2100 mm

Battery capacity

10 min to 20 min to be calculated

Not included

Not included

Color

RAL 7035

RAL 7035

RAL 7035

 

2.2 TSI MODULE AGIL 20 kVA

Model

TSI AGIL

Nominal Output Power

20 kVA / 14 kW

Nominal input voltage

230VAC +/-15%

3x400V+N +/- 15%

Input Power factor

1

Nominal output voltage

230VAC

3x400V+N

Dimensions (mm)

483 x 133.4 x 600 (W x H x D)

Weight

Approximately 24 kg

Operating T°

-10 to +40 °C

 

2.3 AC INPUT DATA

Model

20 – 60 kVA

40 to 160 kVA

40 to 160 kVA

Nominal output power per module (kVA/kW)

20kVA/14 kW

20kVA/14 kW

20kVA/14 kW

Number of module installed / max module installable

1 / 3

2 / 8

2 / 8 per frame

Max 4 frames in //

Nominla input power max

Including load, battery and efficiency

60kW

160 kW

640 kW

Nominal input voltage

230VAC +/-15%

3x400V+N +/- 15%

230VAC +/-15%

3x400V+N +/- 15%

230VAC +/-15%

3x400V+N +/- 15%

Input voltage range

170VAC to 264 VAC for = 100% power available for the load

150VAC to 170VAC brownout (17,7 kVA per module @ 150VAC)

3x294VAC+N to 3x457VAC+N for = 100% power available for the load

3x260VAC+N to 3x294VAC+N brownout (17,7 kVA per module @ 260VAC)

Input frequency

47 Hz to 63 Hz

Input power factor

PF = 0,99 at 100% load

 

 According with settings and configuration, the input current will be increase up to 150% for 15 sec and 10 In for 20ms. Take care for syzing the upstream breaker.

 

2.4 OUTPUT DATA

Model

20 – 60 kVA

40 to 160 kVA

40 to 160 kVA

Nominal output power per module (kVA/kW)

20kVA/14 kW

20kVA/14 kW

20kVA/14 kW

Number of module installed / max module installable

1 / 3

2 / 8

2 / 8 per frame

Max 4 frames in //

Max. Nominal Power load

60 kVA / 42 kW

160 kVA / 112 kW

4 x 160 kVA = 640 kVA

4 x 112 kW = 448 kW

Output rated voltage

Adjustable from 200VAC to 240 VAC

Nominal power from 210VAC to 240VAC

Adjustable from 3x342VAC+N to 3x415VAC+N

Nominal power from 3x363VAC+N to3x415VAC+N

Output voltage statibiltiy

Static : <= +/-1%

Dynamic (load impact 0% to 100% and 100% to 0%) : +/-3%

Output voltage distorsion

With linear load <+/-2%

With non linear load <+/-4% (EN62040-3-2001)

Nominal output frequency

50Hz or 60Hz

Output frequency tolerence

Free running (If AC input not present) : +/- 0,1%

Synchronised with AC input from 47Hz to 53Hz, or 57Hz to 63Hz. Free running outside this range @ nominal value

Permissible unbalance load

For 3 phase operation 100% each phase regulated independently

Overload capacity

150% 15Sec

110% permanent (depends on ambient T°)

Short Circuit capacity

10xIn during 20 mS under conditions

Crest Factor

3:1

Efficiency AC-AC

100% /75% / 50% / 25%

Efficiency DC-AC

 

97 % / 95 % / 95 % / 93%

97% / 95% / 95% / 92%

 

2.5 BATTERY information

Max Charging current per module

5 kW @ 230Vac input volt. Ref chapter 2.7 for other voltage range

Battery Voltage

400VDC (2x200VDC with middle point)

Nbr of Cells

190 to 200 cells VRLA

Temperature compensated

Yes

Battery Type

VRLA


20 kVA

40kVA

60kVA

160kVA

Nominal DC current at 360 VDC (1,8 VDC /cell)

41 A

82 A

123 A

328 A

Max. Nominal Current rectifier @ 400VDC

12,5

25

37,5

100

 

Power available for battery charge is manage by the Agil modular UPS and is related with input voltage, temperature compensation, battery current limit

Battery cable will adapt with current limitation and fuse.

AGIL description download>>

 
Products Uninterruptible Power Supply Modular UPS CE+T